S11-M Fully Sealed Oil-Immersed Power Transformer is supplied for utility power distribution. CANGO reviews rated data, drawings, quantity, destination, and configuration notes before quotation.
Model
S11-M
Category
Power Transformers
Application
Utility power distribution
Supply Type
Project quotation and technical support

Product Overview

S11-M fully sealed oil-immersed power transformer is designed for electrical energy distribution. It is commonly used for utility power distribution and industrial distribution projects, with the final selection based on rated data, drawings, and site conditions.

utilities, EPC contractors, transformer distributors, industrial project owners, and electrical engineering companies can request configuration review for oil immersed power transformer. Please send capacity, voltage combination, tap range, connection group, cooling or insulation type, loss data, impedance, and installation environment, quantity, destination, and any project standard requirements for quotation.

Model and Meaning

S11-M fully sealed oil-immersed power transformer model and meaning diagram

Key Features

01

Capacity Selection

S11-M: Capacity, high-voltage and low-voltage combination, tap range, and connection group are confirmed before quotation. This point is especially relevant to oil immersed power transformer.
02

Cooling and Insulation

Oil-immersed, dry-type, amorphous alloy, and H-class requirements are reviewed according to installation conditions. For S11-M, check this together with the selected project scheme.
03

Loss Data Review

No-load loss, load loss, impedance, and efficiency-related data should be matched with the selected capacity. On S11-M, confirm the application duty, site layout, and project standard before selection.
04

Project Installation

Foundation, lifting, terminal position, ventilation, and clearance requirements need confirmation before delivery. Use the S11-M drawings and rated data to confirm this point before quotation.
05

Application Flexibility

Transformer selection can support utility, industrial, commercial, indoor, outdoor, and renewable-energy projects. For S11-M, review this with oil immersed power transformer and the final installation plan.

Technical Specifications

Main Product Performance Parameters of S11 10 kV Double-Winding Series

ModelRated capacity (kVA)Connection groupHigh voltage (kV)Tap range (%)Low voltage (kV)No-load loss (kW)Load loss (kW)No-load current (%)Short-circuit impedance (%)
S11-M-3030Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.1000.630/0.6001.54
S11-M-5050Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.1300.910/0.8701.34
S11-M-6363Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.1501.09/1.041.24
S11-M-8080Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.1801.31/1.251.24
S11-M-100100Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.2001.58/1.501.14
S11-M-125125Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.2401.89/1.801.14
S11-M-160160Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.2802.31/2.2014
S11-M-200200Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.3402.73/2.6014
S11-M-250250Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.4003.20/3.050.94
S11-M-315315Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.4803.83/3.650.94
S11-M-400400Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.5704.52/4.300.84
S11-M-500500Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.6805.41/5.150.84
S11-M-630630Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.8106.200.64.5
S11-M-800800Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.40.9807.500.64.5
S11-M-10001000Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.41.1510.30.64.5
S11-M-12501250Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.41.3612.00.54.5
S11-M-16001600Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.41.6414.500.54.5
S11-M-20002000Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.41.9418.30.45
S11-M-25002500Dyn11 / Yzn11 / Yyn06 / 6.3 / 10 / 10.5+/-2 x 2.5% / +/-5%0.42.2921.20.45
For capacities up to 500 kVA, load-loss values before/after the slash apply to Dyn11 or Yzn11 / Yyn0 connection groups respectively. The source also notes that the highest operating efficiency is obtained at an annual average load rate of 35%-40% when the listed loss values are used.

Main Product Performance Parameters of S11 20 kV Double-Winding Series

ModelRated capacity (kVA)Connection groupHigh voltage (kV)Tap range (%)Low voltage (kV)No-load loss (kW)Load loss (kW)No-load current (%)Short-circuit impedance (%)
S11-M-3030Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.090.662.15.5
S11-M-5050Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.130.9625.5
S11-M-6363Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.151.1451.95.5
S11-M-8080Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.181.371.85.5
S11-M-100100Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.21.651.65.5
S11-M-125125Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.241.981.55.5
S11-M-160160Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.292.421.45.5
S11-M-200200Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.332.861.35.5
S11-M-250250Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.43.351.25.5
S11-M-315315Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.484.011.15.5
S11-M-400400Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.574.7315.5
S11-M-500500Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.685.6615.5
S11-M-630630Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.816.820.96
S11-M-800800Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.40.988.251.86
S11-M-10001000Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.41.1511.330.76
S11-M-12501250Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.41.3613.20.76
S11-M-16001600Dyn1120+/-5%; +/-2 x 2.5% for selected capacities0.41.6415.950.66
The 20 kV transformer can be supplied with dual-voltage high-voltage wiring according to project requirements, allowing switching between 20 kV and 10 kV network inputs.

Insulation Level

Voltage level (kV)Maximum operating voltage (kV)1 min power-frequency withstand voltage (kV)Lightning impulse full wave (kV)Lightning impulse cut wave (kV)
0.40.4657585
1012357585
202355125140

Installation Dimensions / Drawing

ForS11-M, confirm the capacity-specific outline dimensions, installation base, terminal position, cooling clearance, and lifting / handling requirements. Use the confirmed technical table, project drawing, and site installation plan as the final dimensional reference before ordering or installation.

Applications

S11-M is mainly selected for utility power distribution and industrial distribution projects. The final application should match the confirmed oil immersed power transformer, rated data, and site installation conditions.
  • Utility power distribution
  • Industrial distribution projects
  • Projects requiring sealed oil-immersed transformers

Customization Options

Cooling Method

Oil-immersed, dry-type, natural cooling, forced-air, or special cooling requirements should be confirmed by model and site condition. Apply this review to S11-M and its oil immersed power transformer.

Winding Material

Copper or aluminum winding requirements should be confirmed when the project specification requires a fixed material. Apply this review to S11-M and its oil immersed power transformer.

Loss Data

No-load loss, load loss, impedance voltage, and efficiency information should be checked against the selected capacity. Apply this review to S11-M and its oil immersed power transformer.

Installation Method

Indoor, outdoor, foundation, ventilation, lifting, terminal position, and clearance requirements should be provided before quotation. Apply this review to S11-M and its oil immersed power transformer.

Cooling Method and Winding Material

Cooling Review

Confirm oil-immersed, dry-type, natural cooling, forced-air, or other cooling requirements according to the installation site. Apply this review to S11-M and its oil immersed power transformer.

Winding Requirement

State copper or aluminum winding requirements when the project specification defines the material. Apply this review to S11-M and its oil immersed power transformer.

Loss Data and Efficiency Information

Performance Data

No-load loss, load loss, impedance, noise, and temperature rise should be reviewed for the selected capacity. Apply this review to S11-M and its oil immersed power transformer.

Efficiency Review

Energy-efficiency level or local efficiency requirements should be confirmed before quotation if required by the project. Apply this review to S11-M and its oil immersed power transformer.

Ordering Instructions / Information Required for Quotation

ForS11-M, send capacity, voltage combination, tap range, connection group, cooling or insulation type, loss data, impedance, and installation environment, quantity, destination, and the expected delivery schedule. The engineering review will be based on the selected oil immersed power transformer and project drawing.

ORDERING INSTRUCTIONS

  • State the required S11-M configuration, quantity, project destination, and intended application.
  • Provide capacity, voltage combination, tap range, connection group, impedance, loss data, cooling or insulation type, and installation environment for technical review.
  • Confirm confirm the capacity-specific outline dimensions, installation base, terminal position, cooling clearance, and lifting / handling requirements before final production or installation planning.
  • List any special environmental, wiring, communication, metering, protection, or component requirements in the inquiry.

Technical Support & Documentation

FAQ

What applications is S11-M used for?
S11-M is used for Utility power distribution, Industrial distribution projects, Projects requiring sealed oil-immersed transformers. The final selection should match the project voltage, current, circuit arrangement, and installation conditions.
Which buyers commonly source S11-M?
utilities, EPC contractors, transformer distributors, industrial project owners, and electrical engineering companies commonly use this product for project-based electrical distribution, installation, replacement, or system expansion work.
Which rated voltage or current should be confirmed for S11-M?
Confirm the rated voltage, rated current, short-circuit level, frequency, protection level, and configuration shown in the technical specifications before quotation.
CanS11-M be configured for a specific project?
Yes.CANGO can review project-specific configurations according to drawings, rated data, protection requirements, component requirements, and site conditions before quotation.
Which standards should be confirmed?
Applicable standards depend on the project and destination market. State IEC, local utility, component, testing, or documentation requirements in the inquiry.
What installation information is required?
S11-M should be matched with the final project drawing and outline data before installation. Send the cabinet scheme or layout requirement for review.
What information is needed for quotation?
For quotation, send transformer type and required capacity, high-voltage and low-voltage rated voltage, frequency, phase, tap range, and connection group, cooling method, insulation type, and winding material requirement, quantity, project country, delivery requirement, and any special component or environmental requirements.
How is delivery time confirmed for S11-M?
Delivery time depends on the confirmed configuration, quantity, component selection, documentation requirement, and production schedule. Share the project deadline during inquiry.

Related Products

Contact / Inquiry CTA

Send project data for S11-M. The fields below are the recommended information for quotation and technical review.
Use the buttons below to send the project request by email or open the contact page. If you have drawings, attach the file in the email or share a file link in the message.

Request Quotation for S11-M

This is project-based power distribution equipment. Share the single-line diagram, rated data, cabinet arrangement, quantity, and destination, and CANGO will review the configuration before quotation.