ZW32-12MG/630 is a 12 kV, three-phase 50 Hz permanent-magnet outdoor vacuum circuit breaker for opening and closing load, overload, and short-circuit currents. It is used in substations, industrial and mining distribution systems, and rural networks requiring frequent outdoor switching.
Its compact, lightweight construction is designed for resistance to condensation and reduced maintenance in demanding climates and polluted environments. The permanent-magnet operating mechanism provides holding force in both open and closed positions, reducing mechanical parts and shortening the transmission chain to support operating reliability and mechanical life.
Utilities, EPC contractors, electrical distributors, and project buyers should provide the short-circuit level, control and protection requirements, pole arrangement, service conditions, quantity, and destination. CANGO reviews the required measurement and protection control box, accessories, and installation drawing before quotation.
Environmental Conditions for Use
Ambient air temperature: -45 degC to +40 degC
Relative humidity: daily average <= 90%; monthly average <= 90%
Altitude:<= 3000 m; when the altitude is increased, the rated level should be increased accordingly
Air pollution level: not exceeding Class IV
Installation location: free from flammable or explosive hazards, chemical corrosion, and severe vibration
Model and Meaning
ZW: outdoor vacuum circuit breaker
32: design sequence number
12: rated voltage, kV
630: rated current, A
20: rated short-circuit breaking current, kA
M: permanent-magnet operating mechanism
Key Features
01
Permanent-Magnet Operation
ZW32-12MG/630: The M designation identifies a permanent-magnet operating mechanism that holds the breaker in the open or closed position. This point is especially relevant to permanent-magnet outdoor breaker with pole-mounted control and protection arrangement.
02
Reduced Mechanical Chain
Fewer mechanical parts and a shorter transmission chain support operating reliability and mechanical endurance. For ZW32-12MG/630, check this together with the selected project scheme.
03
Compact Outdoor Design
The product sheet identifies compact size, low weight, condensation resistance, and reduced maintenance as design characteristics. On ZW32-12MG/630, confirm the application duty, site layout, and project standard before selection.
04
Control-Box Integration
The installation arrangement can incorporate a measurement and protection control box for feeder monitoring and protection. Use the ZW32-12MG/630 drawings and rated data to confirm this point before quotation.
05
Adverse-Site Capability
The specified service conditions cover low temperature, high altitude, humidity, and Class IV pollution environments. For ZW32-12MG/630, review this with permanent-magnet outdoor breaker with pole-mounted control and protection arrangement and the final installation plan.
Technical Specifications
ZW32-12MG/630 Technical Parameter Table
Review the ZW32-12MG/630 values, units, rated data, and project requirements before quotation.
Item
Unit
Data
Rated voltage
kV
12
Rated insulation level
1 min power-frequency withstand voltage
Dry: to earth / phase-to-phase / across open contacts
kV
42 / 42 / 48
Wet: external insulation to earth
kV
34
Lightning impulse withstand voltage (peak)
To earth / phase-to-phase / across open contacts
kV
75 / 75 / 85
Rated frequency
Hz
50
Rated current
A
630
Rated short-circuit breaking current
kA
12.5 / 16 / 20
Rated short-circuit making current (peak)
kA
31.5 / 40 / 50
Rated peak withstand current
kA
31.5 / 40 / 50
4 s rated short-time withstand current
kA
20
Rated operating sequence
O-0.3s-CO-180s-CO
Closing time / opening time
ms
25-50 / 15-50
Rated short-circuit breaking operations
operations
30
Mechanical endurance
operations
10000
1 min power-frequency withstand voltage of control and auxiliary circuits
V
2000
Rated operating voltage and auxiliary-circuit rated voltage
V
DC 220 / AC 220
Overcurrent release
Rated current
A
5
Tripping-current accuracy
%
+/-10
Installation Dimensions / Drawing
ZW32-12MG/630 single-pole and double-pole installation arrangements with outline dimensions for project layout review.
Applications
ZW32-12MG/630 is mainly selected for substation feeder protection and control and industrial and mining distribution networks. The final application should match the confirmed permanent-magnet outdoor breaker with pole-mounted control and protection arrangement, rated data, and site installation conditions.
Substation feeder protection and control
Industrial and mining distribution networks
Rural distribution systems with frequent operation
Single-pole or double-pole outdoor feeder installations
Customization Options
Control and Protection
Confirm protection, measurement, communication, reclosing, and permanent-magnet control requirements. Apply this review to ZW32-12MG/630 and its permanent-magnet outdoor breaker with pole-mounted control and protection arrangement.
Pole Arrangement
Provide the required single-pole or double-pole installation arrangement and mounting details. Apply this review to ZW32-12MG/630 and its permanent-magnet outdoor breaker with pole-mounted control and protection arrangement.
Voltage Transformer
State whether the installation requires the voltage transformer shown in the reference arrangement. Apply this review to ZW32-12MG/630 and its permanent-magnet outdoor breaker with pole-mounted control and protection arrangement.
Auxiliary Supply
Confirm DC 220 V or AC 220 V operating and auxiliary-circuit voltage. Apply this review to ZW32-12MG/630 and its permanent-magnet outdoor breaker with pole-mounted control and protection arrangement.
Permanent-Magnet Operating System
Holding Principle
The permanent magnet provides holding force in both the open and closed positions. Apply this review to ZW32-12MG/630 and its permanent-magnet outdoor breaker with pole-mounted control and protection arrangement.
Mechanical Arrangement
Reduced mechanical parts and a shorter transmission chain support reliability and mechanical life. Apply this review to ZW32-12MG/630 and its permanent-magnet outdoor breaker with pole-mounted control and protection arrangement.
Protection and Control Interface
Control Box
Confirm the measurement and protection control box, communication, power supply, and protection logic. Apply this review to ZW32-12MG/630 and its permanent-magnet outdoor breaker with pole-mounted control and protection arrangement.
Protection Duty
Select 12.5 kA, 16 kA, or 20 kA short-circuit breaking duty according to the feeder study. Apply this review to ZW32-12MG/630 and its permanent-magnet outdoor breaker with pole-mounted control and protection arrangement.
Pole-Mounted Installation
Installation Scheme
Review the single-pole or double-pole arrangement, source side, load side, voltage transformer, and support structure. Apply this review to ZW32-12MG/630 and its permanent-magnet outdoor breaker with pole-mounted control and protection arrangement.
Outline Review
Use the extracted drawing to confirm phase spacing, dimensions, mounting holes, and site clearances. Apply this review to ZW32-12MG/630 and its permanent-magnet outdoor breaker with pole-mounted control and protection arrangement.
Ordering Instructions / Information Required for Quotation
ForZW32-12MG/630, send short-circuit level, permanent-magnet control, protection and measurement functions, auxiliary supply, pole arrangement, and site conditions, quantity, destination, and the expected delivery schedule. The engineering review will be based on the selected permanent-magnet outdoor breaker with pole-mounted control and protection arrangement and project drawing.
ORDERING INSTRUCTIONS
Confirm rated current and the required rated short-circuit breaking current.
Provide permanent-magnet control, protection, measurement, communication, and auxiliary-power requirements.
Provide the single-pole or double-pole installation arrangement and state whether a voltage transformer and control box are required.
Provide site conditions, quantity, destination country, applicable standard, and delivery requirements.
ZW32-12MG/630 is used for Substation feeder protection and control, Industrial and mining distribution networks, Rural distribution systems with frequent operation. The final selection should match the project voltage, current, circuit arrangement, and installation conditions.
Which buyers commonly source ZW32-12MG/630?
utilities, EPC contractors, electrical distributors, rural-grid contractors, and industrial project buyers commonly use this product for project-based electrical distribution, installation, replacement, or system expansion work.
Which rated voltage or current should be confirmed for ZW32-12MG/630?
Confirm the rated voltage, rated current, short-circuit level, frequency, protection level, and configuration shown in the technical specifications before quotation.
CanZW32-12MG/630 be configured for a specific project?
Yes.CANGO can review project-specific configurations according to drawings, rated data, protection requirements, component requirements, and site conditions before quotation.
Which standards should be confirmed?
Applicable standards depend on the project and destination market. State IEC, local utility, component, testing, or documentation requirements in the inquiry.
What installation information is required?
ZW32-12MG/630 should be matched with the final project drawing and outline data before installation. Send the cabinet scheme or layout requirement for review.
What information is needed for quotation?
For quotation, send rated voltage, rated current, and short-circuit level, permanent-magnet control and auxiliary-power requirements, protection, measurement, communication, and control-box requirements, single-pole or double-pole installation arrangement, quantity, project country, delivery requirement, and any special component or environmental requirements.
How is delivery time confirmed for ZW32-12MG/630?
Delivery time depends on the confirmed configuration, quantity, component selection, documentation requirement, and production schedule. Share the project deadline during inquiry.
Send project data for ZW32-12MG/630. The fields below are the recommended information for quotation and technical review.
Use the buttons below to send the project request by email or open the contact page. If you have drawings, attach the file in the email or share a file link in the message.
This is project-based power distribution equipment. Share the single-line diagram, rated data, cabinet arrangement, quantity, and destination, and CANGO will review the configuration before quotation.